Flaton-flex A is a tape that foams up in case of fire for fire protection sealing of structural joints in walls or ceilings. Specially developed for joints up to 10 mm.
Flaton-flex A is 100 mm wide, flexible and is attached to the wooden component by means of staples when installed in the middle of the joint.
Its mode of action is based on the formation of a heat-insulating foam in case of fire. Joints are filled by the material that forms and prevent the passage of fire, heat and smoke in the case of fire.
- Flaton-flex A has building material class B2 according to DIN 4102
- halogen-, antimony-, silicone- and solvent-free
- tested in accordance with DIN 1366-4 for joints in timber construction
- EI 90 proven
Fire resistance | EI 90 |
Building material class | C-s1,d0 |
Joint widths | 5 / 10 mm |
Wall joints
Execution | Classification according to DIN EN 13501-2 |
Timber / Timber | EI 90-V-X-F-W 10 |
Timber / solid component | EI 90-V-X-F-W 5 |
Ceiling joint
Execution | Classification according to DIN EN 13501-2 |
Timber / Timber | EI 90-V-X-F-W 10 |
Timber / solid component | EI 90-V-X-F-W 5 |
Joints between wall and ceiling
Execution | Classification according to DIN EN 13501-2 |
Timber / Timber | EI 90-V-X-F-W 5 |
Wall joints with Flaton-flex A:
Timber component – timber component: joint up to 10 mm
Timber component – solid component: joint up to 5 mm
Ceiling joints and joints between ceilings and rising walls with Flaton-flex A:
Timber component – timber component: Joint up to 10 mm
Timber component – solid component: joint up to 5 mm
Ceiling-wall connection joints with Flaton-flex A:
Timber component – timber component: Joint up to 5 mm
Note on the components:
Solid components must have a component thickness > 150 mm and a bulk density of at least 650 ± 200 kg/m³.
Timber components must have a component thickness > 120 mm in a wall and > 160 mm in a ceiling.
Flaton-flex A is supplied as a 15m roll. The width is 100mm, the thickness 2mm.
Before installing Flaton-flex A, the inner flanks of the joint should be cleaned. In the case of solid construction elements, formwork, concrete splashes etc. must be removed.
Flaton-flex A is simply applied to the middle of the joint on the timber component using staples before the components are installed. The elements are to be laid butt to butt on the front side. No further fixing is necessary.
Alternatively, Flaton-flex A can also be applied to prefabricated elements during production after consultation.
Classification of solid ceilings and walls wood/wood and wood/ aerated concrete with installed Rex “Flaton-flex A” joint seals in various installation states without mechanically induced movement of the joint width of fire resistance class EI 90 in accordance with DIN EN 1366-4: 2021-05:
- Joint seal Rex “Flaton-flex A” with joint width solid component joint 5 mm wood/wood in horizontal test setup: Fire resistance class EI 90-H-X-F-W5
- Joint sealing Rex “Flaton-flex A” with joint width solid component joint 10 mm wood/wood in horizontal test setup: Fire resistance class EI 90-H-X-F-W10
- Joint sealing Rex “Flaton-flex A” with joint width solid component joint 5 mm wood/ aerated concrete in horizontal test setup: Fire resistance class EI 90-H-X-F-W5
- Joint sealing Rex “Flaton-flex A” with joint width solid component joint 5 mm wood/wood in vertical test setup: Fire resistance class EI 90-V-X-F-W5
- Joint sealing Rex “Flaton-flex A” with joint width solid component joint 10 mm wood/wood in vertical test setup: Fire resistance class EI-90-V-X-F-W10
- Joint sealing Rex “Flaton-flex A” with joint width solid component joint 5 mm wood/ aerated concrete in vertical test setup: Fire resistance class EI 90-V-X-F-W5
(Classification report on fire resistance no. KB 3.2/22-042-3, MFPA Leipzig GmbH, Leipzig, 17.10.2022)
Classification of a horizontal wall joint with installed joint seal Rex “Flaton-flex A”, which connects to a ceiling, according to tested alignment “D” of DIN EN 1366-4: 2021-05, section 13 without mechanically induced movement of the joint width with solid timber components of fire resistance class EI 90 in accordance with DIN EN 1366-4: 2021-05:
- Joint seal Rex “Flaton-flex A” with joint width solid component joint 5 mm timber/timber in horizontal test setup: Fire resistance class EI 90-H-X-F-W5
(Classification report on fire resistance no. KB 3.2/22-042-4, MFPA Leipzig GmbH, Leipzig, 18.10.2022)
-
UP TO10mmJOINT WIDTH BETWEEN TIMBER COMPONENTS
-
UP TOEl 5mmJOINT WIDTH FOR WOODEN AND SOLID COMPONENTS
-
UP TOEl 90FIRE RESISTANCE