Classified fire protection joint filler for structural joints up to a joint width of 10 mm.
Flaton joint sealant is a strip-shaped joint element that foams up in the event of fire for fire-protection sealing of structural joints in walls or ceilings. The Flaton joint seal consists of a 2.5 mm thick Flaton VPG 12 fire protection board (approval Z-19.11-457 of the German Institute for Building Technology) and a laminated melamine resin foam (5 mm). The layer of 5 mm melamine foam is used for compressible clamping of the joint seal into the joint. The mode of action is based on the formation of a heat-insulating foam in the event of fire. Joints are filled by the foam and prevent the passage of fire, heat and smoke in the event of fire.
- volume increase of the flaton layer in case of fire: at least 4.5-fold according to the approval
- regularly measured volume increase is 11-fold
- can be used in space-enclosing components made of aerated concrete with a bulk density of 650 ± 200 kg/m³ or higher bulk densities in normal concrete, hollow blocks and masonry
Fire resistance: | EI 180 |
Building material class: | B-s1,d0 according to DIN EN 13501-1 |
Joint widths: | 10 mm |
Wall joints (vertical – max. joint width 10 mm – minimum wall thickness 100 mm)
Execution | Joint lt. KB | Classification according to DIN EN 13501-2 |
1000 x 40 x 8 mm | W4 | EI 180-V-X-F-W 10 |
1000 x 40 x 8 mm | W4 | EI 180-V-X-F-W 10 |
Ceiling joint (horizontal – max. joint width 10 mm – minimum ceiling thickness 150 mm)
Execution | Joint lt. KB | Classification according to DIN EN 13501-2 |
1000 x 40 x 8 mm | D4 | EI 180-H-X-F-W 10 |
- European Technical Assessment according to EAD 350141-00-1106 ETA-20/0686 (DIBt, Berlin)
- Classification report on fire resistance according to DIN EN 13501-2: KB 3.2/20-019-2 (MFPA Leipzig GmbH, Leipzig)
- Classification report on fire behaviour according to DIN EN 13501-1: K-2301/856/20-MPA BS (MPA Braunschweig, Braunschweig)
- General building authority approval for the building material Flaton VPG 12: Z-19.11-457 (Deutsches Institut für Bautechnik, Berlin)
-